Collection: Isolated Signal Converter
3系列隔离器
1.1 LW3051 (1 In 1 Out)
The signal isolator provides isolation transmission between field devices and control room equipment, enabling mutual conversion of different signals. It supplies isolated DC power to 2-wire/3-wire transmitters and detects 4~20mA current signals from transmitters. After isolation and anti-interference processing, it outputs DC current or voltage signals to control systems or other instrumentation. This isolator uses DC power supply with triple isolation between input, output, and power. It suppresses common mode interference, normal mode interference, and spike pulses, ensuring stable and reliable signal transmission in control systems.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 50mA
Input
- Input signals: 4~20mADC, 0~20mADC, 0~10mADC (configurable DC current ranges); 1~5VDC, 0~5VDC, 0~10VDC (configurable DC voltage ranges)
- Input impedance: 50Ω (current input)
- Power supply voltage for transmitter: 18~28VDC
- Maximum input current limit: Approximately 30mADC
Output
- Output signals: 4~20mADC, 0~20mADC, 0~10mADC (configurable DC current ranges); 1~5VDC, 0~5VDC, 0~10VDC (configurable DC voltage ranges)
- Allowable load for current output: 0~500Ω
- Output ripple: <50mVp-p
Comprehensive Technical Parameters
- Transmission accuracy: ±0.1%F·S
- Temperature drift: ±0.01%F·S/℃
- Power supply variation effect: 0.05% (within allowable voltage range)
- Response time: <10ms
- Ambient temperature: -20℃~+60℃
- Humidity range: 5~95%RH (non-condensing)
- Insulation resistance: ≥100MΩ/500VDC
- Dielectric strength: ≥1500VAC/1min
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC control systems, connecting 2-wire/3-wire/4-wire transmitters
- 35mm standard DIN rail mounting; Connection cable cross-section 0.5~2.5mm² single/multi-core cable, secured with M3 slotted cylinder head screws
1.2 LW3052 (1 In 1 Out, with Lightning Surge Protection)
Surge protection with 5KA current discharge capability; Safe and reliable, protecting systems from lightning strikes, space-saving and wiring-saving design. It provides isolated DC power to field transmitters and detects 4~20mA current signals from transmitters. After isolation and interference suppression processing, it outputs DC current or voltage signals to control systems or other instrumentation. This isolator uses DC power supply with triple isolation between input, output, and power. It suppresses common mode interference, normal mode interference, and spike pulses, ensuring stable and reliable signal transmission in control systems.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 50mA
Input
- Input signals: 4~20mADC, 0~20mADC, 0~10mADC (configurable DC current ranges)
- Input impedance: 50Ω
- Power supply voltage for transmitter: 18~28VDC
- Maximum input current limit: Approximately 30mADC
- Surge protection capability: 5KA current discharge
Output
- Output signals: 4~20mADC, 0~20mADC, 0~10mADC (configurable DC current ranges); 1~5VDC, 0~5VDC, 0~10VDC (configurable DC voltage ranges)
- Allowable load for current output: 0~500Ω
- Output ripple: <50mVp-p
Comprehensive Technical Parameters
- Same as LW3051 (transmission accuracy, temperature drift, etc.)
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, connecting 2-wire/4-wire transmitters, suitable for lightning-prone environments
- 35mm standard DIN rail mounting; Supports 2-wire/4-wire input via dip switch
1.3 LW3053 (1 In 2 Out)
The signal isolator provides isolation transmission between field devices and control room equipment, enabling mutual conversion of different signals. It supplies isolated DC power to 2-wire/3-wire transmitters and detects 4~20mA current signals from transmitters. After isolation and anti-interference processing, it outputs two independent DC current or voltage signals to control systems or other instrumentation. This isolator uses DC power supply with triple isolation between input, output, and power. It suppresses common mode interference, normal mode interference, and spike pulses, ensuring stable and reliable signal transmission in control systems.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 60mA
Input
- Same as LW3051 (current/voltage signals optional, 18~28VDC power supply)
Output
- Two independent outputs, each with signal types same as LW3051 (4~20mA/voltage optional)
- Allowable load for each current output: 0~500Ω
- Output ripple for each channel: <50mVp-p
Comprehensive Technical Parameters
- Same as LW3051
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, distributing signals to two control systems, connecting 2-wire/3-wire/4-wire transmitters
- 35mm standard DIN rail mounting
1.4 LW3054 (2 In 2 Out)
The signal isolator provides isolation transmission for two independent signals between field devices and control room equipment, enabling mutual conversion of different signals. It supplies isolated DC power to two 2-wire/3-wire transmitters respectively and detects 4~20mA current signals from transmitters. After isolation and anti-interference processing, it outputs two independent DC current or voltage signals to control systems. This isolator uses DC power supply with triple isolation between input, output, and power. It suppresses common mode interference, normal mode interference, and spike pulses, ensuring stable and reliable signal transmission in control systems.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 95mA
Input
- Two independent inputs, each same as LW3051 (current/voltage signals optional, 18~28VDC power supply per channel)
- Input impedance per channel: 50Ω (current input)
- Maximum input current limit per channel: Approximately 30mADC
Output
- Two independent outputs, each same as LW3051
Comprehensive Technical Parameters
- Same as LW3051
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, processing two parallel signals, connecting two 2-wire/3-wire/4-wire transmitters
- 35mm standard DIN rail mounting
1.5 LW3055 (1 In 3 Out)
The signal isolator provides isolation transmission between field devices and control room equipment, enabling mutual conversion of different signals. It supplies isolated DC power to 2-wire/3-wire transmitters and detects 4~20mA current signals from transmitters. After isolation and anti-interference processing, it outputs three independent DC current or voltage signals to control systems or other instrumentation. This isolator uses DC power supply with triple isolation between input, output, and power. It suppresses common mode interference, normal mode interference, and spike pulses, ensuring stable and reliable signal transmission in control systems.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 70mA
Input
- Same as LW3051
Output
- Three independent outputs, each same as LW3051
- Allowable load for each current output: 0~500Ω
Comprehensive Technical Parameters
- Same as LW3051
Dimensions (L×H×W)
- 110mm×120mm×18mm
Application & Installation
- Compatible with DCS/PLC, distributing signals to three control systems, connecting 2-wire/3-wire/4-wire transmitters
- 35mm standard DIN rail mounting
1.6 LW3056 (1 In 4 Out)
The signal isolator provides isolation transmission between field devices and control room equipment, enabling mutual conversion of different signals. It supplies isolated DC power to 2-wire/3-wire transmitters and detects 4~20mA current signals from transmitters. After isolation and anti-interference processing, it outputs four independent DC current or voltage signals to control systems or other instrumentation. This isolator uses DC power supply with triple isolation between input, output, and power. It suppresses common mode interference, normal mode interference, and spike pulses, ensuring stable and reliable signal transmission in control systems.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 100mA
Input
- Same as LW3051
Output
- Four independent outputs, each same as LW3051
- Allowable load for each current output: 0~500Ω
Comprehensive Technical Parameters
- Same as LW3051
Dimensions (L×H×W)
- 110mm×120mm×18mm
Application & Installation
- Compatible with DCS/PLC, distributing signals to four control systems, connecting 2-wire/3-wire/4-wire transmitters
- 35mm standard DIN rail mounting
1.7 LW3057 (1 In 2 Out, with Lightning Surge Protection)
Surge protection with 5KA current discharge capability; Safe and reliable, protecting systems from lightning strikes, space-saving and wiring-saving design. It provides isolated DC power to field transmitters and detects 4~20mA current signals from transmitters. After isolation and interference suppression processing, it outputs two independent DC current or voltage signals to control systems or other instrumentation. This isolator uses DC power supply with triple isolation between input, output, and power. It suppresses common mode interference, normal mode interference, and spike pulses, ensuring stable and reliable signal transmission in control systems.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 60mA
Input
- Same as LW3052 (with 5KA surge protection, current signal input, 18~28VDC power supply)
Output
- Two independent outputs, each same as LW3052
- Allowable load for each current output: 0~500Ω
Comprehensive Technical Parameters
- Same as LW3051
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, distributing signals to two systems in lightning-prone environments, connecting 2-wire/4-wire transmitters
- 35mm standard DIN rail mounting, supports 2-wire/4-wire input via dip switch
1.8 LW3058 (1 In 1 Out, Active/Passive Switchable)
The signal isolator provides isolation transmission between field devices and control room equipment, enabling mutual conversion of different signals. It supplies isolated DC power to 2-wire/3-wire transmitters and detects 4~20mA current signals from transmitters. After isolation and anti-interference processing, it outputs DC current signals to control systems or other instrumentation. This isolator uses DC power supply with triple isolation between input, output, and power. It suppresses common mode interference, normal mode interference, and spike pulses, ensuring stable and reliable signal transmission in control systems; Output active or output loop power supply can be selected via panel dip switch with unchanged wiring.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 50mA
Input
- Input signals: 4~20mADC, 0~20mADC, 0~10mADC (configurable DC current ranges)
- Input impedance: 50Ω
- Power supply voltage for transmitter: 18~28VDC
- Maximum input current limit: Approximately 30mADC
Output
- Output signals: 4~20mADC, 0~20mADC, 0~10mADC (configurable DC current ranges)
- Allowable load for current output: 0~500Ω
- Output ripple: <10mVp-p (different from other analog input isolators)
- Output mode: Active/passive switchable via dip switch
Comprehensive Technical Parameters
- Same as LW3051
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, connecting 2-wire/3-wire/4-wire transmitters, suitable for scenarios requiring active/passive output switching
- 35mm standard DIN rail mounting
2.1 LW3045 (1 In 1 Out)
Receives DC signals from control systems, and after isolation and interference suppression processing, outputs DC current or voltage signals to various field devices. It outputs DC current or voltage signals to control systems or other instrumentation. This isolator uses DC power supply with triple isolation between input, output, and power. It suppresses common mode interference, normal mode interference, and spike pulses, ensuring stable and reliable signal transmission in control systems.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 50mA
Input
- Input current: 4~20mADC, 0~20mADC, 0~10mADC (configurable DC current ranges), input impedance ≤100Ω
- Input voltage: 1~5VDC, 0~5VDC, 0~10VDC (configurable DC voltage ranges), input impedance ≥500KΩ
Output
- Output current: 4~20mADC, 0~20mADC, 0~10mADC (configurable DC current ranges), allowable load 0~750Ω (different from analog input isolators)
- Output voltage: 1~5VDC, 0~5VDC, 0~10VDC (configurable DC voltage ranges)
- Output ripple: <50mVp-p
Comprehensive Technical Parameters
- Transmission accuracy: ±0.1%F·S
- Temperature drift: ±0.01%F·S/℃
- Power supply variation effect: 0.05% (within allowable voltage range)
- Response time: <10ms
- Ambient temperature: -20℃~+60℃
- Humidity range: 5~95%RH (non-condensing)
- Insulation resistance: ≥100MΩ/500VDC
- Dielectric strength: ≥1500VAC/1min
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, driving valve positioners, electrical converters and other field devices
- 35mm standard DIN rail mounting; Connection cable cross-section 0.5~2.5mm²
2.2 LW3005 (2 In 2 Out)
Receives two DC signals from control systems, and after isolation and interference suppression processing, outputs two independent DC current or voltage signals to various field devices. It outputs DC current or voltage signals to control systems or other instrumentation. This isolator uses DC power supply with triple isolation between input, output, and power. It suppresses common mode interference, normal mode interference, and spike pulses, ensuring stable and reliable signal transmission in control systems.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 95mA
Input
- Two independent inputs, each with input types same as LW3045 (current/voltage optional, consistent impedance matching)
Output
- Two independent outputs, each with output types same as LW3045 (current load 0~750Ω, ripple <50mVp-p)
Comprehensive Technical Parameters
- Same as LW3045
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, driving two valve positioners, electrical converters and other field devices
- 35mm standard DIN rail mounting
3.1 LW3927 (1 In 1 Out, RTD/Thermocouple Configurable)
This product receives thermocouple or RTD signals, and after isolation and linearization processing, converts them into linearized DC signals output to control systems or other instrumentation. It can be connected to a computer via USB TYPE-C interface to configure signal types and range settings. This temperature transmitter uses an independent DC power supply with triple isolation between input, output, and power.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 40mA
Input
- Input RTD: Pt100, Pt1000, Ni1000, Cu50, Cu100, etc.
- Input thermocouple: K, J, E, T, N, R, S, B, W-Re, etc.
- Excitation current: 0.5mA
- Lead resistance: 0~20Ω (for 2-wire or 3-wire with consistent length)
Output
- Output current: 4~20mADC, 0~20mADC, 0~10mADC (configurable DC current ranges), allowable load 0~500Ω
- Output voltage: 1~5VDC, 0~5VDC, 0~10VDC (configurable DC voltage ranges)
- Output ripple: <10mVp-p
Comprehensive Technical Parameters
- Transmission accuracy: ±0.1%F·S
- Temperature drift: ±0.01%F·S/℃
- Power supply variation effect: 0.05% (within allowable voltage range)
- Response time: <500ms (different from analog isolators' <10ms)
- Ambient temperature: -20℃~+60℃
- Humidity range: 5~95%RH (non-condensing)
- Insulation resistance: ≥100MΩ/500VDC
- Dielectric strength: ≥1500VAC/1min
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, connecting thermocouple or RTD sensors, suitable for scenarios requiring on-line configuration of signal types
- 35mm standard DIN rail mounting; Supports USB TYPE-C configuration
3.2 LW3928 (1 In 2 Out, RTD/Thermocouple Configurable)
This product receives thermocouple or RTD signals, and after isolation and linearization processing, converts them into two independent linearized DC signals output to control systems or other instrumentation. It can be connected to a computer via USB TYPE-C interface to configure signal types and range settings. This temperature transmitter uses an independent DC power supply with triple isolation between input, output, and power.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 60mA
Input
- Same as LW3927 (consistent RTD/thermocouple types, excitation current 0.5mA)
Output
- Two independent outputs, each same as LW3927 (current load 0~500Ω, ripple <10mVp-p)
Comprehensive Technical Parameters
- Same as LW3927 (response time <500ms)
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, connecting thermocouple or RTD sensors, distributing signals to two systems requiring configuration
- 35mm standard DIN rail mounting
3.3 LW3921 (2 In 2 Out, RTD/Thermocouple Configurable)
This product receives two thermocouple or RTD signals, and after isolation and linearization processing, converts them into two independent linearized DC signals output to control systems or other instrumentation. It can be connected to a computer via USB TYPE-C interface to configure signal types and range settings. This temperature transmitter uses an independent DC power supply with triple isolation between input, output, and power.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 90mA
Input
- Two independent inputs, each same as LW3927 (RTD/thermocouple types optional, excitation current 0.5mA per channel)
Output
- Two independent outputs, each same as LW3927
Comprehensive Technical Parameters
- Same as LW3927
Dimensions (L×H×W)
- 110mm×120mm×18mm
Application & Installation
- Compatible with DCS/PLC, connecting two thermocouple or RTD sensors requiring separate configuration
- 35mm standard DIN rail mounting
4.1 LW3011 (1 In 1 Out)
Receives passive switch contacts or proximity sensor signals, and after isolation, transmits them to control systems or other instrumentation via relay contacts, level signals, or transistor outputs. This signal isolator uses DC power supply with triple isolation between input, output, and power. It suppresses common mode interference, normal mode interference, and spike pulses, ensuring stable and reliable signal transmission in control systems.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 30mA
Input
- Input signal: NAMUR type proximity sensor conforming to DIN19234 standard
- Active signal judgment: "ON" when input signal >2.1mA, "OFF" when <2.1mA
- Open circuit voltage: 8V±0.5V
- Short circuit current: Approximately 4mA
- Switching threshold: Approximately 1.55mA
- Hysteresis: 0.2~0.4mA
Output
- Relay contact (normally open): Contact capacity 2A/30VDC (resistive load), contact resistance ≤0.2Ω
- Level signal: High level 22~26VDC, low level 0~1VDC, load resistance ≥1KΩ
- Transistor output: External power supply voltage ≤40V, output current ≤40mA; Collector output high level=VCC, low level ≤2.5V; Emitter output high level=VCC-2.5V, low level ≤0.5V
Comprehensive Technical Parameters
- Ambient temperature: -20℃~+60℃
- Storage temperature: -40℃~+80℃
- Humidity range: 5~95%RH (non-condensing)
- Insulation resistance: ≥100MΩ/500VDC
- Dielectric strength: ≥1500VAC/1min
Dimensions (L×H×W)
- 110mm×120mm×18mm
Application & Installation
- Compatible with DCS/PLC, connecting switches (mechanical contacts) or NAMUR type proximity sensors
- 35mm standard DIN rail mounting; With power supply and switch status indicators
4.2 LW3012 (1 In 2 Out)
Receives passive switch contacts or proximity sensor signals, and after isolation, transmits them to control systems or other instrumentation via relay contacts, level signals, or transistor outputs (two independent outputs). This signal isolator uses DC power supply with triple isolation between input, output, and power. It suppresses common mode interference, normal mode interference, and spike pulses, ensuring stable and reliable signal transmission in control systems.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 40mA
Input
- Same as LW3011 (NAMUR signal, consistent threshold and hysteresis)
Output
- Two independent outputs, each with output types same as LW3011 (relay/level/transistor optional)
- Relay contact capacity per channel: 2A/30VDC (resistive load)
Comprehensive Technical Parameters
- Same as LW3011
Dimensions (L×H×W)
- 110mm×120mm×18mm
Application & Installation
- Compatible with DCS/PLC, connecting switches or NAMUR type proximity sensors, distributing signals to two systems
- 35mm standard DIN rail mounting
4.3 LW3022 (2 In 2 Out)
Receives two passive switch contacts or proximity sensor signals, and after isolation, transmits them to control systems or other instrumentation via relay contacts, level signals, or transistor outputs (two independent outputs). This signal isolator uses DC power supply with triple isolation between input, output, and power. It suppresses common mode interference, normal mode interference, and spike pulses, ensuring stable and reliable signal transmission in control systems.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 50mA
Input
- Two independent inputs, each same as LW3011 (NAMUR signal, threshold approximately 1.55mA per channel)
Output
- Two independent outputs, each same as LW3011
Comprehensive Technical Parameters
- Same as LW3011
Dimensions (L×H×W)
- 110mm×120mm×18mm
Application & Installation
- Compatible with DCS/PLC, connecting two switches or NAMUR type proximity sensors
- 35mm standard DIN rail mounting
5.1 LW3700 (1 In 1 Out)
A passive isolator with 4~20mA current signal input and 4~20mA current signal output. No external power supply is required during use, as its operating energy is derived from the signal current. Passive isolators effectively solve potential problems in signal interconnection and suppress possible interference during signal transmission. This passive isolator provides electromagnetic isolation between input and output circuits.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- No external power required, energy derived from input signal current
Input
- Current signal input: 4~20mADC
- Equivalent input impedance: 100Ω + load resistance (at 20mA input)
- Voltage drop: ≤2V (at 20mADC)
- Overload current: ≤35mA
Output
- Output current: 4~20mADC
- Output load resistance (RL) calculation: RL≤(Ui-Ud)÷0.02 (Ui is input loop voltage, Ud is voltage drop)
- Output ripple: <50mVp-p
Comprehensive Technical Parameters
- Transmission accuracy: ±0.1%F·S (at 100Ω load)
- Load variation effect: ±0.1% (per 100Ω load increase)
- Temperature drift: ±0.01%F·S/℃
- Response time: <10ms
- Ambient temperature: -20℃~+60℃
- Humidity range: 5~95%RH (non-condensing)
- Dielectric strength: ≥1500VAC/1min
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, connecting 4~20mA current sources, suitable for scenarios without additional power supply
- 35mm standard DIN rail mounting; Connection cable cross-section 0.5~2.5mm²
5.2 LW3720 (2 In 2 Out)
A passive isolator with two channels of 4~20mA current signal input and 4~20mA current signal output. No external power supply is required during use, as its operating energy is derived from the signal current. Passive isolators effectively solve potential problems in signal interconnection and suppress possible interference during signal transmission. This passive isolator provides electromagnetic isolation between input and output circuits.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- No external power required
Input
- Two independent inputs, each same as LW3700 (4~20mADC, voltage drop ≤2V@20mA)
Output
- Two independent outputs, each same as LW3700 (4~20mADC, consistent load calculation formula)
Comprehensive Technical Parameters
- Same as LW3700
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, connecting two channels of 4~20mA current sources
- 35mm standard DIN rail mounting
5.3 LW3730 (3 In 3 Out)
A passive isolator with three channels of 4~20mA current signal input and 4~20mA current signal output. No external power supply is required during use, as its operating energy is derived from the signal current. Passive isolators effectively solve potential problems in signal interconnection and suppress possible interference during signal transmission. This passive isolator provides electromagnetic isolation between input and output circuits.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- No external power required
Input
- Three independent inputs, each same as LW3700 (4~20mADC, voltage drop ≤2V@20mA)
Output
- Three independent outputs, each same as LW3700 (4~20mADC, consistent load calculation formula)
- Output ripple: <50mVp-p
Comprehensive Technical Parameters
- Same as LW3700
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, connecting three channels of 4~20mA current sources
- 35mm standard DIN rail mounting
6.1 LW3711 (1 In 1 Out)
The passive transmitter power supply provides power to field 2-wire transmitters and transmits their signals with loop power supply. Input and output are isolated from each other to enhance control system anti-interference capability. No working power supply required. Supports bidirectional HART signal transmission.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Loop-powered, no external working power required
Input
- Power supply for transmitter: 18~28VDC
- Current capacity: Below 22mADC
- Overload protection: Approximately 30mADC
Output
- Output form: 2-wire current loop DC4~20mA
- Maximum load resistance: ≤350Ω
- Loop supply voltage: 12~35VDC
- Maximum output current: 30mADC
Comprehensive Technical Parameters
- Transmission accuracy: ±0.1%F·S (at 100Ω load)
- Load variation effect: ±0.1% (per 100Ω load increase)
- Temperature drift: ±0.01%F·S/℃
- Response time: <10ms
- Ambient temperature: -20℃~+60℃
- Humidity range: 5~95%RH (non-condensing)
- Insulation resistance: ≥100MΩ/500VDC
- Dielectric strength: ≥1500VAC/1min
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, powering 2-wire transmitters and transmitting signals, supporting HART bidirectional communication
- 35mm standard DIN rail mounting
7.1 LW3024 (1 In 1 Out, Passive Thermocouple)
The passive thermocouple temperature transmitter converts thermocouple temperature sensor signals into DC4~20mA current signals. Input and output are isolated from each other to enhance control system anti-interference capability. Loop-powered. HART communication function is optional and should be specified when ordering.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Loop-powered, no external power required
Input
- Input specifications: Thermocouples K, J, E, T, N, R, S, B, W-Re, etc., with any thermocouple range
- Input type: Voltage sensor, above 3mV
- Input resistance: Above 500KΩ
- Fusing detection current: 0.1μA
- Cold junction compensation: Automatic, compensation range -5~55℃, compensation error ±0.5℃
- Sensor fusing handling: Output as maximum current
Output
- Output form: 2-wire current loop 4~20mADC
- Loop supply voltage: 12~35VDC
- Maximum output current: 25mADC
- Load capacity: =(supply voltage-12)/0.02
Comprehensive Technical Parameters
- Transmission accuracy: ±0.1%F·S (at 250Ω load)
- Temperature drift: ±0.01%F·S/℃
- Power supply variation effect: ±0.1% (300Ω load change)
- Response time: <500ms
- Ambient temperature: -20℃~+60℃
- Humidity range: 5~95%RH (non-condensing)
- Insulation resistance: ≥100MΩ/500VDC
- Dielectric strength: ≥1500VAC/1min
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, connecting thermocouple sensors, optional HART communication
- 35mm standard DIN rail mounting
7.2 LW3027 (1 In 1 Out, Passive RTD)
The passive RTD temperature transmitter converts RTD temperature sensor signals into DC4~20mA or other signals. Both 2-wire and 3-wire RTDs can be input. Input and output are isolated from each other to enhance control system anti-interference capability. Loop-powered. HART communication function is optional and should be specified when ordering.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Loop-powered, no external power required
Input
- Input specifications: RTD Pt100, Ni1000, Cu50, Cu100, etc.
- Lead resistance: 0~20Ω
- Excitation current: 1mA
Output
- Same as LW3024 (2-wire 4~20mADC, load capacity=(supply voltage-12)/0.02)
Comprehensive Technical Parameters
- Transmission accuracy: ±0.1%F·S (at 250Ω load)
- Other parameters (temperature drift, response time, etc.) same as LW3024
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, connecting 2-wire/3-wire RTD sensors, optional HART communication
- 35mm standard DIN rail mounting
8.1 LW3048 (1 In 1 Out, RS-485)
Communication signal isolator,实现RS485半双工信号的双向通信,并可以向现场设备提供一组隔离电源。该信号隔离器采用直流电源供电,输入-输出-电源三端隔离,使控制系统信号传输更稳定可靠。
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption: ≤150mA (at 24V supply, with 24V, 50mA power distribution)
Input
- Communication terminals: Between terminals 7 and 8 (standard RS-485 communication)
- Power distribution terminals: Between terminals 9 and 10 for field device power supply, optional 5V/100mA, 9V/50mA, 12V/50mA, 15V/50mA (specify parameters when ordering, special parameters can be customized)
Output
- Output type: Standard RS-485 digital signal (half-duplex)
- Signal level rules: Standard RS-485 differential level
- Transmission delay: ≤10μs
- Signal transmission rate: ≤256kbps
Comprehensive Technical Parameters
- Maximum baud rate: 300~115200bps (automatic serial port signal detection)
- Transmission distance: 1200m
- Ambient temperature: -20℃~+60℃
- Insulation resistance: ≥100MΩ/500VDC
- Dielectric strength: ≥1500VAC/1min, 50Hz
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, connecting standard RS485 signal devices, suitable for scenarios requiring isolated power supply
- 35mm standard DIN rail mounting
8.2 LW3085 (1 In 1 Out, CAN)
Communication signal isolator,实现CAN半双工信号的双向通信,并可以向现场设备提供一组隔离电源。该信号隔离器采用直流电源供电,输入-输出-电源三端隔离,使控制系统信号传输更稳定可靠。
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): ≤160mA (at 100mA output), ≤120mA (at 50mA output)
Input
- Signal type: Standard CAN half-duplex signal
- Signal speed: CAN ≤1Mbps
- Power distribution options: 6V/100mA, 9V/50mA, 12V/50mA, 24V/50mA (specify parameters when ordering)
- Power distribution switch settings (K3, K2, K1): 24V/50mA (OFF-OFF-OFF), 12V/50mA (ON-OFF-OFF), 9V/50mA (ON-ON-OFF), 6V/100mA (ON-ON-ON)
Output
- Signal type: Standard CAN half-duplex signal
- Signal speed: CAN ≤1Mbps
Comprehensive Technical Parameters
- Response time: <10ms
- Ambient temperature: -20℃~+60℃
- Insulation resistance: ≥100MΩ/500VDC
- Dielectric strength: ≥1500VAC/1min, 50Hz
Dimensions (L×H×W)
- 110mm×120mm×13mm
Application & Installation
- Compatible with DCS/PLC, connecting standard CAN half-duplex signal devices
- 35mm standard DIN rail mounting
9.1 LW3086 (1 In 1 Out)
Inputs frequency signals, after isolation, shaping and amplification, according to user requirements, can optionally output isolated current signals, voltage signals, frequency signals or relay switch signals, etc., can provide power supply to field primary instruments or sensors, this product requires independent power supply, with triple isolation between input, output and power, with online fault self-diagnosis function, can configure signal types, signal ranges, etc. through PC configuration software, can be used with various instruments and DCS, PLC.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 18~36VDC (power reverse protection)
- Power distribution voltage: 6V, 9V, 12V, 15V optional (0.9W MAX)
Input
- Input signal: Frequency pulse signal
- Frequency range: 0.1~100kHz
- Pulse width: ≥5μs
- Input impedance: 1.5KΩ
- Signal trigger: Low level 0~2V, high level 4~24V
- Signal resolution: 0.1Hz
- Amplitude limit: ≤30Vpp
Output
- Current output: 0(4)~20mA, load capacity ≤550Ω (loop power supply optional)
- Voltage output: 0(1)~5V (load ≥1MΩ), 0(2)~10V (load ≥2MΩ)
- Frequency output: Collector output, emitter output (load resistance ≥2kΩ)
- Relay output (specify parameters when ordering)
Comprehensive Technical Parameters
- System transmission accuracy: ±0.1%F·S (25±2℃)
- Temperature coefficient: 40ppm/℃ (typical value)
- Electromagnetic compatibility: IEC61326-3-1
- Dielectric strength: ≥3000VAC (optocoupler isolation), ≥1500VAC (electromagnetic isolation)
- Response time: 0.5s (10%~90%)
- Operating temperature: -20℃~+60℃
- Storage temperature: -40℃~+80℃
- Insulation resistance: ≥100MΩ/500VDC
- Dielectric strength: ≥1500VAC/1min, 50Hz
Dimensions (L×H×W)
- 110mm×120mm×18mm
Application & Installation
- Compatible with DCS/PLC, processing frequency signals, suitable for scenarios requiring configurable output types
- 35mm standard DIN rail mounting
9.2 LW3087 (1 In 2 Out)
Inputs frequency signals, after isolation, shaping and amplification, according to user requirements, can optionally output two independent isolated current signals, voltage signals, frequency signals or relay switch signals, etc., can provide power supply to field primary instruments or sensors, this product requires independent power supply, with triple isolation between input, output and power, with online fault self-diagnosis function, can configure signal types, signal ranges, etc. through PC configuration software, can be used with various instruments and DCS, PLC.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Same as LW3086 (18~36VDC, power distribution 6/9/12/15V optional)
Input
- Same as LW3086 (frequency 0.1~100kHz, pulse width ≥5μs)
Output
- Two independent outputs, each with output types same as LW3086 (current/voltage/frequency/relay optional)
Comprehensive Technical Parameters
- Same as LW3086
Dimensions (L×H×W)
- 110mm×120mm×18mm
Application & Installation
- Compatible with DCS/PLC, processing frequency signals and distributing to two systems, suitable for scenarios requiring configurable output
- 35mm standard DIN rail mounting
9.3 LW3088 (2 In 2 Out)
Inputs two frequency signals, after isolation, shaping and amplification, according to user requirements, can optionally output two independent isolated current signals, voltage signals, frequency signals or relay switch signals, etc., can provide power supply to field primary instruments or sensors, this product requires independent power supply, with triple isolation between input, output and power, with online fault self-diagnosis function, can configure signal types, signal ranges, etc. through PC configuration software, can be used with various instruments and DCS, PLC.
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Same as LW3086
Input
- Two independent inputs, each same as LW3086 (frequency 0.1~100kHz, independent power distribution per channel)
Output
- Two independent outputs, each same as LW3086
Comprehensive Technical Parameters
- Same as LW3086
Dimensions (L×H×W)
- 110mm×120mm×18mm
Application & Installation
- Compatible with DCS/PLC, processing two frequency signals requiring separate configuration of outputs
- 35mm standard DIN rail mounting
10.1 LW3019 (1 In 2 Out)
实现了热电阻信号的隔离转换,输入热电阻信号,变送输出隔离的电阻信号或电流信号,实现输入、输出及电源之间的电气隔离。该信号隔离器用直流电源供电,输入-输出-电源三端隔离,使得检测和控制回路的信号稳定性和抗干扰能力大大增强,从而提高了控制系统的可靠性。设置有USB接口,与计算机连接,可在线组态设置;具有断线故障诊断报警功能,带有报警指示灯,报警时电源指示灯闪烁。
        
                Main Technical Specifications
                Expand
            
            Power Supply
- Voltage range: 20~30VDC
- Rated voltage: 24VDC
- Current consumption (at 24VDC): Approximately 70mA
Input
- Input RTD: Pt100 (range is any RTD range, specify parameters when ordering)
- Lead resistance: ≤20Ω
- Allowable input signal: 2-wire/3-wire RTD 0~350Ω
Output
- Output signal 1: 1:1 resistance output
- Output signal 2: Current signal (4~20mA, etc.), allowable load 0~500Ω
- Out-of-range output: 0~20mA
- Output voltage: 1~5VDC, 0~5VDC, 0~10VDC (configurable DC voltage ranges)
- Output ripple: <10mVp-p
Comprehensive Technical Parameters
- Transmission accuracy: ±0.2%F·S
- Temperature drift: ≤50ppm/℃ (-20~+60℃)
- Response time: <2s
- Ambient temperature: -20℃~+60℃
- Humidity range: 5~95%RH (non-condensing)
- Insulation resistance: ≥100MΩ/500VDC
- Dielectric strength: ≥1500VAC/1min, 50Hz
Dimensions (L×H×W)
- 110mm×120mm×18mm
Application & Installation
- Compatible with DCS/PLC, connecting RTD sensors, suitable for scenarios requiring isolated conversion of resistance/current signals with wire break alarm
- 35mm standard DIN rail mounting; Supports USB online configuration